To Order Call: 800-817-3486 or Email: sales@mpimorheat.com or Fill a Contact Form

Mid Temp Self-Regulating Heating Cable (250F)

Standard Lead Times

Information

Ideal for pipe tracing, freeze protection, and low temperature process maintenance applications up to 250°F (120°C).

Self-limiting: Automatically adjusts heat output based on surface temperature.

Safe to overlap and insulate.

Can be cut-to-length and terminated in the field.

No temperature controller is required. (If a specific process temperature is needed, a temperature controller is required.)

Specifications
  • Continuous maintenance temperature: 250°F (120°C) maximum
  • Intermittent exposure temperature: 366°F (185°C) maximum; -40°F (-40°C) minumum
  • 5, 10, or 15 watts/ft (16, 33, 49 watts/m)
  • Supply voltages: 110 – 120VAC or 208 – 277VAC
  • Moisture, chemical, and flame resistant
  • 16AWG bus wires
  • Tinned copper braid resistance: 0.003 ohms/ft (0.010 ohms/m)
  • T-Rating: T3**

 

** Electrical equipment T-rating codes define the maximum surface temperature that equipment will reach. It is used in hazardous (classified) area applications.

Selecting Heater Length

Outer Layer Options

DescriptionDimensionsPurpose
Tinned Copper Metal Braid0.2″ x 0.6″
(6mm x 15mm)
Ordinary applications
Tinned Copper Metal Braid with Fluoropolymer Overjacket0.2″ x 0.6″
(6mm x 15mm)
For use in strong chemical environments (i.e. strong acids)

Maximum Circuit Length in Feet per Circuit Breaker Size

Heat Cable TypeCircuit Breaker SizeStart-up Temperature
50°F 
(10°C)
0°F 
(-20°C)
-40°F 
(-40°C)
5 watt 120 volt15 amp
20 amp
30 amp
150
200
240
135
180
220
130
170
210
5 watt 240 volt15 amp
20 amp
30 amp
250
330
480
230
305
440
220
295
420
10 watt 120 volt15 amp
20 amp
30 amp
90
120
180
85
110
165
80
105
160
10 watt 240 volt15 amp
20 amp
30 amp
140
190
280
130
175
260
125
170
250
15 watt 120 volt15 amp
20 amp
30 amp
70
90
130
65
85
125
60
80
120
15 watt 240 volt15 amp
20 amp
30 amp
100
135
200
95
125
185
90
120
180

Note: Special consideration must be given for the circuit breaker due to the high initial in-rush currents.

Voltage Adjustment

Power Adjustment Factor
Product Type208 VAC277 VAC
5 watt 240 volt0.781.25
10 watt 240 volt0.861.16
15 watt 240 volt0.921.09