WARNING — A ground fault protection device is required by NEC to minimize the danger of fire if the heating cable is damaged or improperly installed. A minimum trip level of 30mA is recommended to minimize nuisance tripping.
| Output | Voltage | Circuit Load | Max.Circuit Length |
| 4 W/Ft. | 120 volt | 0.033 Amps/Ft. | 350 Ft. |
| 8 W/Ft. | 120 volt | 0.067 Amps/Ft. | 240 Ft. |
| 12 W/Ft. | 120 volt | 0.100 Amps/Ft. | 200 Ft. |
| 4 W/Ft. | 240 volt | 0.017 Amps/Ft. | 700 Ft. |
| 8 W/Ft. | 240 volt | 0.033 Amps/Ft. | 480 Ft. |
| 12 W/Ft. | 240 volt | 0.050 Amps/Ft. | 400 Ft. |
| 12 W/Ft. | 480 volt | 0.025 Amps/Ft. | 780 Ft. |