General Constant Wattage Heating Cables

Standard Lead Times

Information
General purpose, dry locations.
NOT APPROVED For Hazardous Locations.
Tinned copper braid for general purpose use.
4, 8 or 12 watts per foot.
120 through 480 volt options
Tinned copper braid for general purpose area use.
Circuit load: 0.033 amps per foot
Maximum circuit length: 350 foot
Maintains temp to 320°F

Our general purpose, constant wattage heating cable is a proven, reliable solution for industrial process temperature maintenance and freeze protection. A parallel heating core produces uniform thermal output over its entire length. Using a single power point, you can easily configure and install a heat tracing system as short as several feet or as long as 780 feet right in the field.
Specifications
  • Uniform Thermal Output, Low Energy Cost
  • No Inrush at Any Ambient
  • Maximum Exposure Temperature, Power Off, 392°F (200°C)
  • Steam Cleanable on Process Equipment Up to 190 PSIG (Power Off)
  • Approximate Size 1/4″W x 1/8″H
  • Minimum Bend Radius 1-1/4″
  • For Use on Metallic Pipes

 

WARNING — A ground fault protection device is required by NEC to minimize the danger of fire if the heating cable is damaged or improperly installed. A minimum trip level of 30mA is recommended to minimize nuisance tripping.

Max Length
Output Voltage Circuit Load Max.Circuit Length
4 W/Ft. 120 volt 0.033 Amps/Ft. 350 Ft.
8 W/Ft. 120 volt 0.067 Amps/Ft. 240 Ft.
12 W/Ft. 120 volt 0.100 Amps/Ft. 200 Ft.
4 W/Ft. 240 volt 0.017 Amps/Ft. 700 Ft.
8 W/Ft. 240 volt 0.033 Amps/Ft. 480 Ft.
12 W/Ft. 240 volt 0.050 Amps/Ft. 400 Ft.
12 W/Ft. 480 volt 0.025 Amps/Ft. 780 Ft.