To Order Call: 800-817-3486 or Email: sales@mpimorheat.com or Fill a Contact Form

Shipped from Stock

Information
STANDARD FEATURES
  • Total 9 profiles, a profile with 16, 32 or 64 segments at most
  • Each segment to be configured as a ramp or dwell(soak)
  • Fast A-D sampling rate (5 times/s)
  • After an event the process goes to run, hold, abort, manual, failure transfer, off mode, next segment or select the second PID values
  • High accuracy of 18-bit A to D input, and 15-bit D to A output
  • The fast sample rate of 200 msec
  • Fuzzy control to reach set point at the least overshooting ans less time
  • Up to three relays are configurable for event output
  • Analog retransmission of process value & set point value
  • Optional RS-485 or 232 communications
  • Programmable port for easy configuration or calibration
  • Lockout protection for security requirement
  • Bumpless transfer of safely control while sensor breaks
  • Digital filter to improve the stability of process value
  • SEL function for easy operation
SPECIFICATIONS
Power
90 – 250 VAC, 47 – 63 Hz, 12VA, 5W maximum
11 – 26 VAC / VDC, SELV, Limited Energy, 12VA, 5W maximum
Signal Input 
Resolution18 bits
Sampling Rate5 times / second
Maximum Rating-2 VDC minimum, 12 VDC maximum( 1 minute for mA input )
Temperature Effect±1.5 uV/ °C for all inputs except mA input 
±3.0 uV/ °C for mA input
Sensor Lead Resistance EffectT/C: 0.2uV/ohm 
3-wire RTD: 2.6 °C/ohm of resistance difference of two leads 
2-wire RTD: 2.6 °C/ohm of resistance sum of two leads
Burn-out Current200nA
Common Mode Rejection Ratio ( CMRR )120dB
Normal Mode Rejection Ratio ( NMRR )55dB
Sensor Break DetectionSensor open for TC, RTD and mV inputs,
Sensor short for RTD input,
below 1 mA for 4-20 mA input,
below 0.25V for 1 – 5 V input, unavailable for other inputs.
Sensor Break Responding TimeWithin 4 seconds for TC, RTD and mV inputs, 
0.1 second for 4-20 mA and 1 – 5 V inputs.
Input
TypeRange Accuracy@ 25 °CInput Impedance
J-120 ~ 1000 °C (-184 ~ 1832 °F)±2 °C2.2MΩ
K-200 ~ 1370 °C (-328 ~ 2498°F)±2 °C2.2MΩ
T-250 ~ 400°C (-418 ~ 752°F)±2 °C2.2MΩ
E-100 ~ 900 °C (-148 ~ 1652 °F)±2 °C2.2MΩ
B0 ~ 1800 °C (32 ~ 3272 °F)±2 °C (200°C – 1800°C)2.2MΩ
R0 ~ 1767.8 °C (32 ~ 3214 °F)±2 °C2.2MΩ
S0 ~ 1767.8 °C (32 ~ 3214 °F)±2 °C2.2MΩ
N-250 ~ 1300 °C (-418 ~ 2372 °F)±2 °C2.2MΩ
L-200 ~ 900 °C (-328 ~ 1652 °F)±2 °C2.2MΩ
PT100 (DIN)-210 ~ 700 °C (-346 ~ 1292 °F)±0.4°C1.3KΩ
PT100 (JIS)-200 ~ 600 °C (-328 ~ 1112 °F)±0.4°C1.3KΩ
mV-8 ~ 70mV±0.05%2.2MΩ
mA-3 ~ 27mA±0.05%70.5Ω
V-1.3 ~ 11.5V±0.05%650KΩ
Output 1 / Output 2 
Relay Rating2A/240 VAC, life cycles 200,000 for resistive load
Pulsed VoltageSource Voltage 5V, current limiting resistance 66Ω .
Output
TypeZero ToleranceSpan ToleranceLoad Capacity
4-20 mA3.6-4 mA20-21 mA500Ω max.
0-20 mA0 mA20-21 mA500Ω max.
0-5 V0 V5-5.25 V10KΩ min.
1-5 V0.9-1 V5-5.25 V10KΩ min.
0-10 V0 V10-10.5 V10KΩ min.
Linear Output 
Resolution15 bits
Output Regulation0.02 % for full load change
Output Settling Time0.1 sec. ( stable to 99.9 % )
Isolation Breakdown Voltage1000 VAC
Temperature Effect±0.01 % of SPAN / °C
Triac ( SSR ) Output 
Rating1A / 240 VAC
Inrush Current20A for a cycle
Min. Load Current50 mA rms
Max. Off-state Leakage3 mA rms
Max. On-state Voltage1.5V rms
Insulation Resistance1000 Mohms min. at 500 VDC
Dielectric Strength2500 VAC for 1 minute
DC Voltage Supply characteristics(Install at Output2)
TypeToleranceMax. Output CurrentRipple VoltageIsolation Brrifer
20V±1V25mA0.2Vp-p500VAC
12V±0.6V40mA0.1Vp-p500VAC
5V±0.25V80mA0.05Vp-p500VAC
Alarm 
Alarm RelayForm C,Max. rating 2A/240VAC, life cycles 200,000 for resistive load.
Alarm FunctionsDwell timer, 
Deviation High / Low Alarm, 
Deviation Band High / Low Alarm 
PV High / Low Alarm
Alarm ModeNormal, Latching, Hold, Latching / Hold.
Dwell Timer0.1 – 4553.6 minutes
Data Communication 
InterfaceRS-232 ( 1 unit ), RS-485 ( up to 247 units )
ProtocolModbus Protocol RTU mode
Address1 – 247
Baud Rate2.4 ~ 38.4 Kbits/s
Parity BitNone, Even or Odd
Stop Bit1 or 2 bits
Communication Buffer64 bytes
Analog Retransmission 
Output Signal4-20 mA, 0-20 mA, 0-1V, 0-5V, 1-5V, 0-10V
Resolution15 bits
Accuracy±0.05 % of span ±0.0025 %/ °C
Load Resistance0 – 500 ohms ( for current output ),10 K ohm minimum ( for voltage output )
Output Regulation0.01 % for full load change
Output Settling Time0.1 sec. (stable to 99.9 % )
Isolation Breakdown Voltage1000 VAC min.
Integral Linearity Error±0.005 % of span
Temperature Effect±0.0025 % of span/ °C
Saturation Low0 mA ( or 0V )
Saturation High22.2 mA ( or 5.55V, 11.1V min. )
Linear Output Range0 – 22.2mA(0-20mA or 4-20mA), 
0 – 5.55V ( 0 – 5V, 1 – 5V ), 
0 – 11.1 V ( 0 – 10V )
User InterfaceDual 4-digit LED Displays
Keypad4 keys
Programming PortFor automatic setup, calibration and testing
Communication PortRS-232 and RS-485
Control Mode 
Output 1Reverse ( heating ) or direct ( cooling )action
Output 2PID cooling control, cooling P band 50 ~ 300% of PB, dead band -36.0 ~ 36.0% of PB
ON-OFF0.1 – 90.0 ( °F ) hysteresis control ( P band = 0 )
P or PD0 – 100.0 % offset adjustment
PIDFuzzy logic modified , Proportional band 0.1 ~ 900.0°F ,
Integral time 0 – 1000 seconds , Derivative time 0 – 360.0 seconds
Cycle Time0.1 – 90.0 seconds
Manual ControlHeat (MV1) and Cool (MV2)
Auto-tuningCold start and warm start
Failure ModeAuto-transfer to manual mode while sensor break or A-D converter damage
Ramping Control0 ~ 900.0°F/minute or 0 ~ 900.0 °F/hour ramp rate
Digital Filter 
FunctionFirst order
Time Constant0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable
Profiler 
Number of profiles9
Number of Segment per profileProfile 1,2,3,4 : 16 
Profile 5,6,7 : 32 
Profile 8,9 : 64
Event Outputs3
Environmental & Physical 
Operating Temperature-10°C ~ 50°C
Storage Temperature-40°C ~ 60°C
Humidity0 to 90 % RH ( non-condensing )
Altitude2000m maximum
PollutionDegree 2
Insulation Resistance20 Mohms min. ( at 500 VDC )
Dielectric Strength2000 VAC, 50/60 Hz for 1 minute
Vibration Resistance10 – 55 Hz, 10 m/s² for 2 hours
Shock Resistance200 m/s² ( 20 g )
MoldingsFlame retardant polycarbonate
DimensionsP41 —96mm(W) X 96mm(H) X 65mm(D), 53 mm depth behind panel
P91 —48mm(W) X 48mm(H) X 116mm(D), 105 mm depth behind panel
WeightP41 — 250 grams 
P91 — 150 grams
Approval StandardsUL 61010C-1 , CSA C22.2 No. 24-93 , 
EN61010-1 (IEC1010-1)
Protective Class
IP65 front panel with additional option,
IP50 front panel without additional option,
all indoor use,
IP 20 housing and terminals with protective cover.
EMCEN61326